Electrical calculators

Wire size calculator

Enter the load, voltage and one-way distance to get the smallest copper or aluminum wire that meets NEC Table 310.16 ampacity and the small-conductor breaker limits, stepped up as needed to keep voltage drop under your limit, plus the breaker size.

Load
A

Sized at 125%.

Circuit
V
ft

Panel to load, one way.

Conductor

75°C for most breakers and lugs; 60°C for ≤100 A unless marked

Advanced options
Voltage drop
%

3% is the NEC informational-note target for a branch circuit or feeder.

Recommended wire size

6 AWG copper

50 A breaker · 65 A at 75°C · 2.05% drop

Breaker or fuse
50 A
Next standard rating at or above 50.00 A (NEC 240.6(A))
Required ampacity
50.00 A
Ambient temperature, bundling and motor loads are not included — see the methodology page.
Minimum size by ampacity
8 AWG
50 A at 75°C, NEC Table 310.16
Voltage drop on 8 AWG
3.26%
7.81 V over 100 ft one way
Ampacity of 6 AWG
65 A
75°C column, NEC Table 310.16
Voltage drop on 6 AWG
4.92 V
235.08 V at the load
Voltage drop, percent
2.05%
Limit 3%
  • 8 AWG carries the load but drops 3.26% over 100 ft; 6 AWG keeps voltage drop under 3% (NEC 210.19 Informational Note).
Wire size: 6 AWG copper on a 50 A breaker8 AWG (50 A, 3.26% drop) beside 6 AWG (65 A, 2.05% drop), drawn to scale by area. Breaker 50 A.8 AWG Cu50 A at 75°C3.26% drop (over 3%)01→6 AWG Cu65 A at 75°C2.05% drop0250 Abreaker03Cross-sections drawn to scale by conductor area
Default example: 50 A at 240 V over 100 ft, copper, 75°C terminations. Circles are drawn to scale by conductor area; the yellow one is the recommended size.
  1. 01 Minimum size by Table 310.16 ampacity
  2. 02 Recommended size for voltage drop
  3. 03 Breaker or fuse rating

How wire size is calculated

The calculator sizes the wire for heat first, then for voltage drop, and takes whichever is bigger.

required ampacity = load amps × 1.25 (continuous load) or × 1 (other loads)

breaker = next standard size at or above the required ampacity (NEC 240.6(A))

Next it walks up NEC Table 310.16, in the column for your termination rating, to the first size whose ampacity covers the required ampacity and that the breaker is allowed to protect. For the small sizes, 240.4(D) sets a hard breaker limit: copper 14 AWG at 15 A, 12 AWG at 20 A, 10 AWG at 30 A; aluminum 12 AWG at 15 A, 10 AWG at 25 A. For larger sizes, 240.4(B) lets you use the next standard breaker above the wire's ampacity when the ampacity is not itself a standard size. Aluminum is not listed below 12 AWG.

voltage drop = 2 × K × load amps × one-way feet ÷ circular mils (single-phase or DC)

voltage drop = 1.732 × K × load amps × one-way feet ÷ circular mils (three-phase)

drop % = voltage drop ÷ circuit voltage × 100

K is 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot), and circular mils come from NEC Chapter 9 Table 8. Voltage drop uses the actual load current, not the 125% figure. If the ampacity size drops more than your limit, the calculator steps up one size at a time until it does not.

Worked example: 50 A at 240 V over 100 ft

The calculator opens on a 50 A noncontinuous load at 240 V single-phase, copper, 75°C terminations, 100 ft one way, with a 3% drop limit.

  1. Required ampacity: 50 A × 1 = 50.00 A. Breaker: 50 A, a standard size.
  2. Table 310.16, copper, 75°C: 8 AWG is rated 50 A, enough for 50 A, and 240.4(D) does not apply to it. Minimum size by ampacity: 8 AWG.
  3. Drop on 8 AWG: 2 × 12.9 × 50 × 100 ÷ 16,510 = 7.81 V, or 3.26% of 240 V. That is over 3%.
  4. Drop on 6 AWG: 2 × 12.9 × 50 × 100 ÷ 26,240 = 4.92 V, or 2.05%.
  5. Result: 6 AWG copper (65 A at 75°C) on a 50 A breaker.

Common sizes by load

Minimum size by Table 310.16 ampacity and the 240.4(D) limits for a noncontinuous load, before voltage drop. Long runs and continuous loads may need a bigger wire.

Smallest conductor by load current; the 60°C column is shown for circuits of 100 A or less.
LoadCopper 60°CCopper 75°CAluminum 75°C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
100 A1 AWG3 AWG1 AWG
125 A—1 AWG2/0 AWG
150 A—1/0 AWG3/0 AWG
200 A—3/0 AWG250 kcmil

Choosing the termination rating

The wire is only as good as the terminal it lands on. NEC 110.14(C) limits terminations on circuits of 100 A or less, or marked for 14 through 1 AWG conductors, to the 60°C column unless the equipment is listed and identified for 75°C. Most modern breakers, panels and lugs are listed 60/75°C, so 75°C is the usual choice; check the label on the breaker and the equipment. Circuits over 100 A, and terminals marked for conductors larger than 1 AWG, use the 75°C column.

  • NM cable (Romex) is sized from the 60°C column (334.80) even though its conductors are rated 90°C.
  • The 90°C column is for derating only: start there when you correct for heat or bundling, then make sure the result does not exceed the termination's column.
  • Aluminum needs terminals marked AL or CU/AL and the right torque.

What this calculator leaves out

It assumes not more than three current-carrying conductors in a raceway or cable and a 30°C (86°F) ambient, the conditions of Table 310.16. It does not apply ambient temperature correction (310.15(B)), adjustment for more than three current-carrying conductors (310.15(C)), the 83% dwelling service and feeder rule of 310.12, or motor circuits sized under Article 430. Hot attics, rooftop conduit, bundled cables and motor or HVAC loads all need those rules. Have an electrician or engineer size services, feeders and anything over these simple cases, and check what your local inspector adopts.

Sources

  • NFPA 70, National Electrical Code, 2023 edition: Table 310.16 (allowable ampacities)
  • NEC 2023 240.4(D): small-conductor overcurrent limits (copper 14 AWG at 15 A, 12 AWG at 20 A, 10 AWG at 30 A; aluminum 12 AWG at 15 A, 10 AWG at 25 A)
  • NEC 2023 240.4(B): next-higher standard overcurrent device rating; 240.6(A) standard ampere ratings
  • NEC 2023 210.19(A)(1) and 210.20(A): continuous loads at 125%
  • NEC 2023 110.14(C): temperature limitations of terminations
  • NEC 2023 Chapter 9 Table 8 conductor areas; trade K-factor voltage-drop method (as in the voltage drop calculator)

Frequently asked questions

How do I pick a wire size from the NEC table?

Start with Table 310.16 in the column that matches the termination temperature, usually 75°C, and find the first size whose ampacity is at least the load (125% for continuous loads). For 14, 12 and 10 AWG, then check the breaker limits in 240.4(D).

Why does 12 AWG copper go on a 20 amp breaker if the table says 25 amps?

NEC 240.4(D) caps the overcurrent device for small conductors regardless of the table. 12 AWG copper is listed at 25 A in the 75°C column but is limited to a 20 A breaker.

What size wire do I need for a 50 amp circuit?

By ampacity at 75°C terminations, 8 AWG copper or 6 AWG aluminum (6 AWG copper if the terminals are 60°C). On long runs, voltage drop pushes copper up a size: at 240 V over 100 ft, 6 AWG copper keeps the drop under 3%.

What is a continuous load and why is it sized at 125%?

A continuous load runs at its maximum current for 3 hours or more, such as an EV charger, water heater or electric heat. The conductor and breaker are sized at 125% of that current (NEC 210.19(A)(1) and 210.20(A)).

Is voltage drop a code requirement?

Not in the NEC itself. Informational notes recommend no more than 3% on a branch circuit or feeder and 5% overall, but they are advisory. Some energy codes adopted for commercial buildings do make voltage-drop limits mandatory.

Can I use the 90°C column to size my wire?

Only as the starting point for derating. Breakers and most lugs are rated 60°C or 75°C, and NEC 110.14(C) limits the final ampacity to the lowest-rated termination.

Is the distance one way or round trip?

One way, from the panel to the load. The 2 in the single-phase formula already accounts for the current coming back on the other conductor.