Minimum insulation R-values for new homes in IECC climate zones 1 through 8 from the 2021 IECC prescriptive table, with the main climate zone for each state and how thick a fiberglass batt is at each R-value.

Minimum R-values by climate zone

Prescriptive minimum insulation R-values for new homes by IECC climate zone
Climate zone Ceiling / attic
R
Wood-frame wall
R
Mass wall
R
Floor
R
Basement wall
R
Slab edge
R, depth
Crawlspace wall
R
0 and 1 3013 or 0+10ci3/413NoneNoneNone
2 4913 or 0+10ci4/613NoneNoneNone
3 4920 or 13+5ci or 0+15ci8/13195ci or 1310ci, 2 ft5ci or 13
4 except Marine 6030 or 20+5ci or 13+10ci or 0+20ci8/131910ci or 1310ci, 4 ft10ci or 13
5 and Marine 4 6030 or 20+5ci or 13+10ci or 0+20ci13/173015ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci
6 6030 or 20+5ci or 13+10ci or 0+20ci15/203015ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci
7 and 8 6030 or 20+5ci or 13+10ci or 0+20ci19/213815ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci
Source: IECC 2021, Table R402.1.3
  • "13+5ci" means R-13 in the stud cavity plus R-5 continuous insulation (rigid foam or similar) over the framing.
  • Mass wall: the second number applies when more than half the insulation is on the interior side of the mass.
  • Slab: R-value of the slab-edge insulation and how far down (or in) from the top of the slab it must extend. Heated slabs also need R-5 under the full slab (footnote d).
  • R-values are minimums for the insulation material only. Section R402.2.1 lets R-38 satisfy an R-49 ceiling, and R-49 satisfy R-60, where the full-height, uncompressed insulation covers the whole ceiling and extends over the wall top plate at the eaves.
  • States and cities adopt the IECC with local amendments, and some still enforce older editions. Confirm the edition in force with your building department.

Climate zones by state

The climate zone covering most of each state’s population, and the other zones found in the state
State Main zone Also has zones
Alabama 32
Alaska 78
Arizona 23, 4, 5
Arkansas 34
California 32, 4, 5, 6
Colorado 54, 6, 7
Connecticut 5—
Delaware 4—
District of Columbia 4—
Florida 21
Georgia 32
Hawaii 1—
Idaho 56
Illinois 54
Indiana 54
Iowa 56
Kansas 45
Kentucky 4—
Louisiana 23
Maine 67
Maryland 45
Massachusetts 5—
Michigan 56, 7
Minnesota 65, 7
Mississippi 32
Missouri 43, 5
Montana 6—
Nebraska 5—
Nevada 34, 5
New Hampshire 56
New Jersey 45
New Mexico 43, 5
New York 45, 6
North Carolina 34, 5
North Dakota 67
Ohio 54
Oklahoma 34
Oregon 45
Pennsylvania 54
Rhode Island 5—
South Carolina 32
South Dakota 65
Tennessee 34
Texas 21, 3, 4
Utah 53, 6
Vermont 6—
Virginia 43, 5
Washington 45, 6
West Virginia 45
Wisconsin 56
Wyoming 65, 7
Source: IECC 2021, Figure R301.1 and Table R301.1 (summarised; county list per PNNL-33270)
  • Zones are assigned by county. Many states span two or more zones, so look up your county in IECC Table R301.1 before choosing a requirement.
  • Moisture regime letters (A moist, B dry, C marine) are omitted here; the R-value table only distinguishes Marine 4.

Batt thickness by R-value

Typical installed thickness of fiberglass batts by R-value
R-value Thickness
in
Type Typical cavity
R-13 3.5Standard2×4 wall
R-15 3.5High-density2×4 wall
R-19 6.25Standard2×6 wall (compressed to 5.5 in it performs at about R-18)
R-21 5.5High-density2×6 wall
R-30 9.5–10Standard2×10 floor or attic
R-38 12–12.5Standard2×12 or attic
R-49 13.5–14StandardAttic (single R-49 batt, or two layers)
R-60 19StandardAttic: two layers (for example R-30 + R-30); no common single R-60 batt
Source: Manufacturer product data (Owens Corning, Knauf, Johns Manville fiberglass batts), typical, Thickness
  • Typical fiberglass values. Mineral wool, cellulose and spray foam reach the same R-value at different thicknesses.
  • Compressing a batt into a shallower cavity lowers its R-value; use the product label for exact figures.

How to read the R-value table

Find your climate zone in the first column, then read across for each part of the building envelope. The numbers are the minimum R-value of the insulation itself under the prescriptive R-value path of the 2021 International Energy Conservation Code (Table R402.1.3). Where a cell lists several options separated by "or", any one of them complies.

Wall entries written as two numbers joined by a plus sign combine cavity insulation and continuous insulation (ci). For example, the zone 5 option 20+5ci means R-20 in the cavity plus R-5 continuous. Mass walls (concrete, block, log) list two values: the higher one applies when most of the insulation is on the inside of the wall.

The slab column gives both an R-value and a depth: R-10 extending 2 ft or 4 ft down from the top of the slab edge (or under the slab), depending on the zone. Zones 1 and 2 have no slab requirement.

Finding your climate zone

The IECC divides the United States into eight thermal zones, plus moisture regimes (A moist, B dry, C marine). Zones run from 1 in south Florida and Hawaii to 8 in interior Alaska. The state table gives the zone covering most of each state's population and the other zones found there; it is a summary only. Look up the county in Table R301.1 for the binding answer.

Batt thickness and fit

A 2×4 wall cavity is 3-1/2 in deep, which holds R-13 or high-density R-15 batts. A 2×6 cavity is 5-1/2 in deep and takes R-19, R-20 or high-density R-21. An R-19 batt is about 6.25 in thick, so it is compressed in a 2×6 wall and performs a little below its label. Attic levels such as R-49 and R-60 are usually reached with blown insulation or two layers of batts laid crosswise.

Common R-value mistakes

  • Using a state's main zone for a county in a colder zone.
  • Compressing batts behind wiring and plumbing, which reduces their R-value.
  • Treating these minimums as targets for an existing home; they apply to new construction and many additions and alterations.
  • Assuming the 2021 table is in force. Many jurisdictions still enforce the 2015 or 2018 IECC, or local amendments.

The table reproduces the 2021 IECC residential prescriptive requirements. Compliance can also be shown with the U-factor alternative or a performance path, which may allow different combinations.

Frequently asked questions

What R-value do I need in my attic?

Under the 2021 IECC (Table R402.1.3): R-30 in zone 1, R-49 in zones 2 and 3, and R-60 in zones 4 through 8. Older editions required less, and your local code may differ.

What R-value is required for 2x4 walls?

In zones 1 and 2, R-13 in a 2×4 cavity meets the 2021 IECC wood-frame wall requirement. Zone 3 requires 20, 13+5ci or 0+15ci, so a 2×4 wall needs R-13 plus R-5 continuous insulation. Zones 4 through 8 require 30, 20+5ci, 13+10ci or 0+20ci (2021 IECC Table R402.1.3).

How thick is R-30 insulation?

About 9.5–10 inches for a standard fiberglass batt. R-38 is about 12–12.5 inches and R-49 about 13.5–14 inches. Blown-in insulation reaches the same R-value at a different depth; check the coverage chart on the bag.

What does "13+5ci" mean?

R-13 insulation in the stud cavity plus R-5 of continuous insulation, usually rigid foam board, installed over the outside of the framing. The 2021 IECC prints it as "13&5ci".

Which climate zone am I in?

Climate zones are assigned by county in IECC Table R301.1 and shown on Figure R301.1. The state list on this page gives the zone most people in each state live in, but many states span several zones.