Box fill chart (NEC 314.16)

The NEC 2023 box fill tables in one place: cubic inches per conductor from Table 314.16(B)(1), what counts toward fill under 314.16(B)(1)–(6), and the volume and conductor limits of standard metal boxes from Table 314.16(A).

Volume allowance per conductor

Free space within a box required for each conductor, by conductor size
Conductor size Volume per conductor
in³
Volume per conductor
cm³
18 AWG 1.5024.6
16 AWG 1.7528.7
14 AWG 2.0032.8
12 AWG 2.2536.9
10 AWG 2.5041.0
8 AWG 3.0049.2
6 AWG 5.0081.9
Source: NEC (NFPA 70) 2023, Table 314.16(B)(1)
  • Metric values are converted at 16.387 cm³ per in³ and rounded; the NEC table prints its own rounded metric figures.
  • Sizes larger than 6 AWG are not counted by volume; boxes for 4 AWG and larger follow the pull-box rules of 314.28.

What counts toward box fill

How many volume allowances each item in a box counts for
Item in the box Counts as
allowances
Allowance based on NEC
Each conductor that enters from outside the box and is spliced or terminated inside 1That conductor’s size314.16(B)(1)
Each conductor that passes through the box without a splice or termination 1That conductor’s size314.16(B)(1)
Each unbroken loop or coil of conductor at least twice the 300.14 free length (12 in or more) 2That conductor’s size314.16(B)(1)
One or more internal cable clamps (all together) 1Largest conductor in the box314.16(B)(2)
Each type of support fitting inside the box (fixture stud, hickey) 1Largest conductor in the box314.16(B)(3)
Each yoke or strap holding a device (switch, receptacle); devices wider than one 2 in gang count 2 per gang 2Largest conductor connected to the device314.16(B)(4)
All equipment grounding conductors and bonding jumpers, up to four 1Largest grounding conductor314.16(B)(5)
Each grounding conductor or bonding jumper beyond the first four (isolated-ground conductors are counted here too; the separate isolated-ground allowance was removed in 2020) 1/4 eachLargest grounding conductor314.16(B)(5)
Each terminal block assembly (new in 2023) 1Largest conductor terminated on the block314.16(B)(6)
Pigtails and jumpers entirely inside the box; grounding conductors and up to four fixture wires smaller than 14 AWG that enter from a domed luminaire or similar canopy and end in the box. Wire connectors are not counted 0—314.16(B)(1) and Exception
Source: NEC (NFPA 70) 2023, 314.16(B)(1)–(6)
  • Total the allowances, multiply each by its Table 314.16(B)(1) volume, and compare the sum with the box volume plus any marked extension ring, plaster ring or domed cover volume.
  • The four-grounds rule and the 1/4-allowance for each additional grounding conductor were added in the 2020 NEC and carried into 2023; the same revision dropped the extra allowance for an isolated-ground set.
  • The 2023 NEC added 314.16(B)(6) for terminal blocks and renumbered the per-conductor table as Table 314.16(B)(1).

Metal box volumes and maximum conductors

Minimum volume of standard metal boxes and the maximum number of conductors of one size, with nothing else in the box
Box Trade size
in
Volume
in³
18 AWG
max
16 AWG
max
14 AWG
max
12 AWG
max
10 AWG
max
8 AWG
max
6 AWG
max
Round / octagonal 4 × 1-1/412.58765552
Round / octagonal 4 × 1-1/215.510876653
Round / octagonal 4 × 2-1/821.51412109874
Square 4 × 1-1/418.0121098763
Square 4 × 1-1/221.01412109874
Square 4 × 2-1/830.32017151312106
Square 4-11/16 × 1-1/425.5171412111085
Square 4-11/16 × 1-1/229.5191614131195
Square 4-11/16 × 2-1/842.02824211816148
Device 3 × 2 × 1-1/27.55433321
Device 3 × 2 × 210.06554432
Device 3 × 2 × 2-1/410.57654432
Device 3 × 2 × 2-1/212.58765542
Device 3 × 2 × 2-3/414.09876542
Device 3 × 2 × 3-1/218.0121098763
Device 4 × 2-1/8 × 1-1/210.36554432
Device 4 × 2-1/8 × 1-7/813.08765542
Device 4 × 2-1/8 × 2-1/814.59876542
Masonry box / gang 3-3/4 × 2 × 2-1/214.09876542
Masonry box / gang 3-3/4 × 2 × 3-1/221.01412109874
FS cast box Single cover/gang (1-3/4)13.59766542
FD cast box Single cover/gang (2-3/8)18.0121098763
FS cast box Multiple cover/gang (1-3/4)18.0121098763
FD cast box Multiple cover/gang (2-3/8)24.016131210984
Source: NEC (NFPA 70) 2023, Table 314.16(A)
  • The conductor maximums assume no clamps, devices, support fittings or grounding conductors. Deduct those allowances first (see the counting rules).
  • Nonmetallic (plastic) boxes and boxes not listed here use the volume marked on the box by the manufacturer (314.16(A)(2)).
  • Trade sizes are length × width × depth for device boxes, diameter or side × depth for round and square boxes.
  • The NEC prints 5 for 8 AWG in a 4 × 1-1/4 in round box, one more than 12.5 ÷ 3.00 in³ allows by volume; the table value is shown as printed.

How to use the box fill tables

Box fill is a volume check. Count every item in the box as a number of conductor "allowances" using the counting-rules table, multiply each allowance by the volume for its conductor size from Table 314.16(B)(1), add them up, and compare the total with the box volume. If the total is larger, use a bigger or deeper box, add an extension ring, or move a splice elsewhere.

The metal-box table gives each box's minimum volume and the most conductors of one size it can hold when nothing else is in it. Those maximums are simply the volume divided by the per-conductor allowance and rounded down, which is how this page computes them. Real boxes almost always contain clamps, a device or grounds, so the true number is lower.

Worked example

A single receptacle in a 3 × 2 × 3-1/2 in metal device box (18 in³), fed by two 12/2 NM cables with internal clamps:

  • Insulated conductors entering the box: 4
  • Internal cable clamps: 1
  • Receptacle on one yoke: 2
  • Equipment grounding conductors (all together): 1

Total 8 allowances × 2.25 in³ = 18.00 in³. That is within the 18 in³ box. Add one more 12/2 cable and the count rises to 10, or 22.50 in³, which no longer fits; a 4 × 2-1/8 in square box with a device ring (30.3 in³ before the ring) would.

Common box fill mistakes

  • Forgetting the two allowances for each device yoke.
  • Counting each ground separately (they count once, up to four) or ignoring them altogether.
  • Using the conductor count from the metal-box table for a box that also holds clamps and a device.
  • Not adding the marked volume of a plaster ring, extension ring or raised cover, which 314.16(A) allows you to include.

Box fill applies to 6 AWG and smaller conductors. Larger conductors fall under the pull and junction box sizing rules in 314.28. Values are from NFPA 70, 2023 edition; local amendments may apply.

Frequently asked questions

How many cubic inches does a 12 gauge wire need in a box?

2.25 cubic inches per conductor. 14 AWG needs 2.00 and 10 AWG needs 2.50 (NEC 2023 Table 314.16(B)(1)).

Do ground wires count in box fill?

Yes, but all of them together count as one conductor of the largest grounding conductor size, up to four. Since the 2020 NEC, each grounding conductor beyond the first four adds a quarter allowance (314.16(B)(5)).

Does a switch or receptacle count as two wires?

Yes. Each device yoke or strap counts as two conductors of the largest wire connected to it. A device wider than a single 2 in gang counts two for each gang it needs (314.16(B)(4)).

Do wire nuts and pigtails count?

No. Wire connectors are not counted, and a conductor that never leaves the box, such as a pigtail, is not counted (314.16(B)(1)).

How do I find the volume of a plastic box?

Nonmetallic boxes are marked with their volume in cubic inches, usually stamped inside the box. Use that marked volume; Table 314.16(A) covers only the standard metal boxes listed in it.