Electrical calculators

Reference chart

Voltage drop chart

How far you can run copper wire at 120 V and 240 V before the voltage drops more than 3%, by wire size and load, with the NEC Chapter 9 conductor data behind the numbers.

Maximum run at 120 volts (3% drop)

Maximum one-way distance in feet for a 3% voltage drop at 120 V, copper, by wire size and load current
Copper size 15 A
ft
20 A
ft
30 A
ft
40 A
ft
50 A
ft
60 A
ft
100 A
ft
14 AWG 38——————
12 AWG 6045—————
10 AWG 967248————
8 AWG 153115765746——
6 AWG 244183122917361—
4 AWG 38829119414511697—
3 AWG 48936724418314612273
2 AWG 61746230823118515492
1 AWG 778583389291233194116
1/0 AWG 982736491368294245147
2/0 AWG 1,238928619464371309185
3/0 AWG 1,5601,170780585468390234
4/0 AWG 1,9681,476984738590492295
Source: NEC (NFPA 70) 2023, Chapter 9 Table 8; K-factor method
  • Distance is one way, from the panel to the load, for a 3% drop (3.6 V) on a single-phase, 2-wire copper circuit, rounded down to the whole foot.
  • Formula: L = VD × CM ÷ (2 × K × I), with K = 12.9 ohm·cmil/ft for copper at 75°C.
  • A dash means the load exceeds the 75°C ampacity of that size or its 240.4(D) breaker limit, so the wire is not a candidate at that current.
  • The 3% target is the informational note to 210.19 (2023 numbering); it is a recommendation, not an enforceable NEC requirement unless adopted locally.

Maximum run at 240 volts (3% drop)

Maximum one-way distance in feet for a 3% voltage drop at 240 V, copper, by wire size and load current
Copper size 15 A
ft
20 A
ft
30 A
ft
40 A
ft
50 A
ft
60 A
ft
100 A
ft
14 AWG 76——————
12 AWG 12191—————
10 AWG 19314496————
8 AWG 30723015311592——
6 AWG 488366244183146122—
4 AWG 776582388291232194—
3 AWG 978734489367293244146
2 AWG 1,234925617462370308185
1 AWG 1,5571,167778583467389233
1/0 AWG 1,9641,473982736589491294
2/0 AWG 2,4761,8571,238928742619371
3/0 AWG 3,1212,3411,5601,170936780468
4/0 AWG 3,9362,9521,9681,4761,181984590
Source: NEC (NFPA 70) 2023, Chapter 9 Table 8; K-factor method
  • Distance is one way, from the panel to the load, for a 3% drop (7.2 V) on a single-phase, 2-wire copper circuit, rounded down to the whole foot.
  • Formula: L = VD × CM ÷ (2 × K × I), with K = 12.9 ohm·cmil/ft for copper at 75°C.
  • A dash means the load exceeds the 75°C ampacity of that size or its 240.4(D) breaker limit, so the wire is not a candidate at that current.
  • Doubling the voltage doubles the allowed drop in volts, so every distance is about twice the 120 V figure.
  • 240 V loads here are single-phase with two current-carrying conductors (no neutral current).

Conductor area and resistance

Conductor area in circular mils and DC resistance at 75°C in ohms per 1,000 feet (stranded, uncoated copper and aluminum)
Size Area
cmil
Copper
Ω/kFT
Aluminum
Ω/kFT
Implied K, copper
Ω·cmil/ft
14 AWG 4,1103.145.1712.9
12 AWG 6,5301.983.2512.9
10 AWG 10,3801.242.0412.9
8 AWG 16,5100.7781.2812.8
6 AWG 26,2400.4910.80812.9
4 AWG 41,7400.3080.50812.9
3 AWG 52,6200.2450.40312.9
2 AWG 66,3600.1940.31912.9
1 AWG 83,6900.1540.25312.9
1/0 AWG 105,6000.1220.20112.9
2/0 AWG 133,1000.09670.15912.9
3/0 AWG 167,8000.07660.12612.9
4/0 AWG 211,6000.06080.112.9
250 kcmil 250,0000.05150.084712.9
300 kcmil 300,0000.04290.070712.9
350 kcmil 350,0000.03670.060512.8
400 kcmil 400,0000.03210.052912.8
500 kcmil 500,0000.02580.042412.9
Source: NEC (NFPA 70) 2023, Chapter 9 Table 8
  • Implied K = resistance × area ÷ 1,000. It sits close to the 12.9 used for copper in the distance tables.
  • Solid 14–8 AWG copper (as in NM cable) is slightly lower: 14 AWG 3.07, 12 AWG 1.93, 10 AWG 1.21, 8 AWG 0.764 ohm/kFT.
  • DC resistance only. For large conductors on AC circuits, Chapter 9 Table 9 (AC impedance) gives a more exact drop.

How to read the voltage drop chart

Pick the row for the copper wire size and the column for the load in amps. The number is the longest one-way run, in feet, that keeps the voltage drop at or below 3% on a single-phase, two-wire circuit. If your run is longer, move down to a larger wire until the distance in that column covers it.

A dash means the wire is too small for that current in the first place: the load exceeds the 75°C ampacity in NEC Table 310.16 or the 240.4(D) breaker limit. Ampacity always comes first; voltage drop only ever pushes the size up. The wire ampacity chart has the full table.

The formula behind it

VD = 2 × K × I × L ÷ CM

VD is the voltage drop in volts, K is the resistivity constant (12.9 ohm-cmil/ft for copper, 21.2 for aluminum, both at 75°C), I is the current in amps, L is the one-way length in feet and CM is the conductor area in circular mils from NEC Chapter 9 Table 8. Rearranged for distance, L = VD × CM ÷ (2 × K × I), which is what generates every cell above.

Worked example: a 16 A load on 12 AWG copper 60 feet from the panel at 120 V gives 2 × 12.9 × 16 × 60 ÷ 6,530 = 3.79 V, or 3.2%. That is just over the 3% target. Moving up to 10 AWG (10,380 cmil) gives 2.39 V, or 2.0%.

Why 240 volts goes twice as far

The drop in volts for a given wire and current is the same at 120 V and 240 V. But 3% of 240 V is twice as many volts as 3% of 120 V, so the allowable distance doubles. That is one reason well pumps, heat pumps and other long-run loads are usually 240 V.

Common voltage drop mistakes

  • Entering the round-trip length; the formula already accounts for both conductors.
  • Using the copper K for aluminum conductors.
  • Ignoring motor starting current, which can briefly cause several times the running drop.
  • Treating the chart as an ampacity table. Check Table 310.16 first.

The K-factor method uses DC resistance. For large conductors on AC circuits, especially in steel conduit, NEC Chapter 9 Table 9 impedance gives a slightly more exact result. Conductor data is from NFPA 70, 2023 edition; local amendments may apply.

Frequently asked questions

How far can I run 12 gauge wire on a 20 amp circuit?

About 45 feet one way at 120 V with a full 20 A load for a 3% drop, using K = 12.9 and 12 AWG at 6,530 circular mils (NEC Chapter 9 Table 8). At 240 V the same wire reaches about 91 feet.

Is a 3% voltage drop required by the NEC?

No. The 3% branch-circuit and 5% total figures appear in informational notes to 210.19 and 215.2(A)(2), which are recommendations. Some jurisdictions and energy codes make them mandatory, and sensitive equipment may need less drop.

Is the distance one way or round trip?

One way: the length of cable from the panel to the load. The formula already doubles it (the 2 in VD = 2·K·I·L ÷ CM) to account for current flowing out and back.

What K value should I use for aluminum?

21.2 ohm-circular mils per foot at 75°C, compared with 12.9 for copper. Aluminum runs therefore reach roughly 61% of the copper distance for the same size and load.

Should I calculate at the breaker rating or the actual load?

Use the actual expected load. Sizing for the full breaker rating is conservative and simple, which is how this chart is built; a calculator lets you enter the real current.

Calculators that use this chart