Voltage drop calculator

Enter the wire size, metal, circuit type, voltage, load current and one-way distance to get the voltage drop in volts and percent, the voltage left at the load, the longest run that stays at 3%, and the smallest wire that keeps the drop at 3%.

Wire
AWG/kcmil

Aluminum starts at 12 AWG.

Circuit

DC and single-phase use the 2-wire formula.

V
A
ft

One way, not round trip.

Voltage drop

4.94 %

5.926 V of 120 V over 75 ft one way

Voltage drop in volts
5.926 V
Voltage at the load
114.07 V
Longest run at 3% drop
45.6 ft
One way, 12 AWG copper at 20 A
Smallest size for 3% drop
8 AWG
1.95% drop in copper at this load and distance
Conductor area
6,530 cmil
K = 12.9 Ω·cmil/ft (copper), multiplier 2
  • Voltage drop 4.94% exceeds the 3% branch-circuit recommendation (NEC 210.19 Informational Note); 8 AWG keeps it under 3%.
Voltage drop 5.926 V (4.94%) over 75 ft of 12 AWG copperSource 120 V, load 114.07 V, 20 A on single-phase ac over 75 ft one way.120 V01SourceLoad12 AWG copper · 6,530 cmilsupply and return conductors75 ft one way02114.07 V03−5.926 V dropVD = 2 × 12.9 × 20 A × 75 ft ÷ 6,530 cmil = 5.926 V (4.94%)04
Default example: 12 AWG copper, 120 V single-phase, 20 A over 75 ft one way. The voltage bars are drawn to scale; the yellow band is the drop.
  1. 01 Source (supply) voltage
  2. 02 One-way length of the run
  3. 03 Voltage at the load; the yellow band is the drop
  4. 04 Formula with your numbers

How voltage drop is calculated

Every foot of wire has a little resistance, so the current flowing to the load loses some voltage along the way. The trade K-factor method turns that into one line of arithmetic using the wire's area in circular mils from NEC Chapter 9 Table 8.

voltage drop (V) = 2 × K × amps × one-way feet ÷ circular mils

three-phase: use √3 (1.732) in place of 2

percent drop = voltage drop ÷ system voltage × 100

voltage at the load = system voltage − voltage drop

K is the resistance of one foot of a one-circular-mil conductor: 12.9 Ω·cmil/ft for copper and 21.2 for aluminum at 75°C. DC and single-phase circuits use 2 because the current goes out on one conductor and back on the other. Turn the formula around and you get the longest run for a 3% drop:

longest run (ft) = 0.03 × system voltage × circular mils ÷ (2 × K × amps)

The calculator then tries each size of the same metal, smallest first (aluminum starts at 12 AWG), and reports the first one that keeps the drop at 3% or less.

Worked example: 20 A over 75 ft of 12 AWG copper

The calculator opens on a 20 A load at the end of a 75 ft run of 12 AWG copper on a 120 V single-phase circuit.

  1. Area of 12 AWG: 6,530 circular mils (Table 8).
  2. Voltage drop: 2 × 12.9 × 20 × 75 ÷ 6,530 = 5.926 V.
  3. Percent drop: 5.926 ÷ 120 × 100 = 4.94%, so the load sees 114.07 V.
  4. Longest run at 3%: 0.03 × 120 × 6,530 ÷ (2 × 12.9 × 20) = 45.6 ft.
  5. 10 AWG would drop 3.11%, still over 3%. 8 AWG drops 1.95%, so 8 AWG is the smallest size that meets 3%.

The 4.94% drop is under the 5% total but over the 3% branch recommendation, so the calculator flags it. A 20 A circuit still needs a conductor rated for the breaker. Upsizing for voltage drop never lets you use a smaller wire than the ampacity tables require.

Voltage drop by wire size and distance

Percent drop for a 20 A load on a 120 V single-phase circuit, copper, by one-way distance. Bold values are over the 3% branch-circuit recommendation.
Wire size50 ft100 ft150 ft200 ft
12 AWG3.3%6.6%9.9%13.2%
10 AWG2.1%4.1%6.2%8.3%
8 AWG1.3%2.6%3.9%5.2%
6 AWG0.8%1.6%2.5%3.3%

For the longest run each size can carry at 3%, at other currents and at 240 V, see the voltage drop chart.

The 3% and 5% recommendations

The NEC does not set a maximum voltage drop for ordinary branch circuits and feeders. The informational note to 210.19 and Informational Note No. 2 to 215.2(A)(2) recommend sizing conductors so that the drop is no more than 3% on a branch circuit or feeder and no more than 5% from the service to the farthest outlet. Informational notes are explanatory material, not enforceable rules.

Excess drop wastes energy as heat in the wire. Motors run hotter and draw more current, lights dim when loads switch on, and electronics may reset or shut down. Long runs to detached garages, wells, outbuildings, gates and EV chargers are where the drop usually becomes the deciding factor in wire size.

Measuring the run and choosing a size

  • Measure the actual path of the wire, not the straight-line distance: up and over walls, along the ceiling, down to the box. Add the slack you leave in panels and boxes.
  • Use the current the load actually draws for long periods. For a branch circuit with several outlets, the load at the far end is the worst case.
  • For a feeder plus a branch circuit, work out each run separately and add the percentages to compare against the 5% total.
  • Size the wire for ampacity first (NEC Table 310.16 and 240.4(D)), then step it up until the drop is acceptable.
  • Larger conductors may not fit the device or breaker terminals. Check the lug ranges, and use a splice or pigtail where the code allows.
  • The K-factor method uses DC resistance. For large conductors on AC circuits, NEC Chapter 9 Table 9 (AC impedance) gives a more exact result.

Sources

  • K-factor method: VD = 2 × K × I × L ÷ CM (single-phase and DC) and √3 × K × I × L ÷ CM (three-phase), K = 12.9 Ω·cmil/ft copper and 21.2 Ω·cmil/ft aluminum at 75°C
  • NFPA 70, National Electrical Code (2023), Chapter 9 Table 8, conductor properties (circular mil areas)
  • NFPA 70, National Electrical Code (2023), 210.19 Informational Note and 215.2(A)(2) Informational Note No. 2 (3% branch or feeder, 5% total)

Frequently asked questions

What is the voltage drop formula?

For DC and single-phase circuits, VD = 2 × K × I × L ÷ CM, where I is the current in amps, L is the one-way length in feet and CM is the conductor area in circular mils. K is 12.9 for copper and 21.2 for aluminum. Three-phase circuits use √3 (1.732) in place of the 2.

How much voltage drop is allowed?

The NEC recommends no more than 3% on a branch circuit or feeder and no more than 5% in total from the service to the farthest outlet (210.19 Informational Note and 215.2(A)(2) Informational Note No. 2). These notes are recommendations, not requirements, unless your jurisdiction or energy code adopts them.

Is the distance one way or round trip?

One way: measure from the panel or source to the load. The 2 in the formula already accounts for the current flowing out on one conductor and back on the other.

How far can I run 12 AWG wire on a 20 A circuit?

At 20 A, 12 AWG copper reaches a 3% drop at about 46 ft one way on 120 V and about 91 ft on 240 V. Lighter loads can run farther; the distance scales inversely with the current.

How much does going up one wire size help?

From 14 through 4 AWG the common sizes skip every other gauge number, so each step up (for example 12 to 10 AWG) gives about 1.59× the area and cuts the drop by roughly 37%. From 4 AWG to 4/0 each step is one gauge number, about 1.26× the area and roughly 21% less drop.

Why does aluminum wire have more voltage drop than copper?

Aluminum has higher resistance for the same area, so its K-factor is 21.2 against 12.9 for copper. The same size aluminum conductor drops about 1.64 times the voltage of copper, which is why aluminum feeders are usually one or two sizes larger.

Why is three-phase voltage drop lower?

On a balanced three-phase circuit the multiplier is √3 (1.732) instead of 2, so for the same current, size and length the drop is about 13% lower than on a single-phase circuit. The percentage is taken of the line-to-line voltage.