HVAC calculators

BTU calculator

Enter the room size, ceiling height, insulation, sun, people and climate to estimate the cooling and heating load in BTU per hour, with the matching window AC size, central tonnage, electric kW and furnace input.

Room
ft

e.g. 12' 6"

ft

e.g. 12' 6"

ft

6 to 20 ft. E.g. 12' 6"

Cooling

+600 BTU/h each beyond 2.

Adds 4,000 BTU/h.

Heating

Older or poorly insulated homes sit at the high end.

Cooling load

8,000 BTU/h

Base 8,000 BTU/h (ENERGY STAR room AC chart). Rule-of-thumb estimate, not an ACCA Manual J load calculation.

Window or room AC
8,000 BTU/h
Smallest standard size that covers the load.
Cooling in tons
0.67 tons
1 ton = 12,000 BTU/h
Heating load
12,000 BTU/h
40 BTU/h per ft² × height × insulation factors
Electric heat
3.5 kW
1 kW = 3,412 BTU/h
Furnace input at 80% AFUE
15,000 BTU/h
Heating load ÷ 0.80
Floor area
300 ft²
Cooling adjustment
1.000
height 1.000 × insulation 1.0 × sun 1.0 × climate 1.0
300 ft² room: 8,000 BTU/h cooling, 12,000 BTU/h heatingPlan 15' by 20', average sun, 2 people. Window unit 8,000 BTU/h.15'20'01300 ft² flooravg sun±0%02032 peopleCooling, BTU/h5k6k8k10k12k14k15k18k24k0central8,000 BTU/h04Window unit: 8,000 BTU/hHeating: 12,000 BTU/h · 3.5 kW
Default example: 15 × 20 ft room, 8 ft ceiling, average sun and insulation, 2 people. The room plan is to scale; the bar shows the cooling load against standard window-unit sizes.
  1. 01 Floor area: 15' × 20' = 300 ft²
  2. 02 Sun exposure: average (×1.0)
  3. 03 Occupants: 2 people
  4. 04 Cooling load: 8,000 BTU/h on the window-unit scale

How BTUs are calculated

The cooling estimate starts from a base for the floor area: 20 BTU/h per square foot, or the ENERGY STAR room air conditioner chart figure for that area if it is larger (it is for most single rooms under about 1,000 ft²). It then scales the base for ceiling height, insulation, sun and climate, and adds fixed amounts for extra people and for cooking.

floor area = length × width

height factor = ceiling height ÷ 8 ft

base = the larger of area × 20 and the ENERGY STAR chart value for the area

cooling = base × height factor × insulation × sun × climate

+ 600 × (people − 2, never below 0) + 4,000 if a kitchen

Cooling is then converted to equipment sizes. A window or room unit is the smallest standard size that covers the load (5,000, 6,000, 8,000, 10,000, 12,000, 14,000, 15,000, 18,000, 24,000 BTU/h). Above 24,000 BTU/h there is no window unit, and the room or zone is central or mini-split territory.

tons = cooling ÷ 12,000

central size = tons rounded up to the next half ton, at least 1.5 tons over 12,000 BTU/h

Heating uses a per-square-foot figure for your climate, scaled by the same height and insulation factors:

heating = area × climate BTU per ft² × height factor × insulation

electric heat (kW) = heating ÷ 3,412

furnace input = heating ÷ 0.80 (an 80% AFUE furnace)

The 80% AFUE furnace is today's federal minimum for gas furnaces; furnaces made from December 18, 2028 must reach 95%, which needs less input for the same heat.

The results show cooling and heating rounded to the nearest 100 BTU/h. Equipment is sold in steps, so more precision than that would be false accuracy.

Worked example: 15 × 20 ft room

The calculator opens on a 15 × 20 ft room with an 8 ft ceiling, average insulation and sun, a moderate climate and 2 people.

  1. Floor area: 15 × 20 = 300 ft². Height factor: 8 ÷ 8 = 1.00.
  2. Cooling base: 300 × 20 = 6,000 BTU/h, less than the ENERGY STAR chart's 8,000 BTU/h for 300 ft², so the base is 8,000. Cooling: 8,000 × 1.0 × 1.0 × 1.0 × 1.0 = 8,000 BTU/h. With 2 people there is no extra people load, and it is not a kitchen, so the total is 8,000 BTU/h.
  3. Equipment: 8,000 ÷ 12,000 = 0.67 ton, so a 8,000 BTU/h window unit covers it.
  4. Heating (moderate climate): 300 × 40 × 1.0 × 1.0 = 12,000 BTU/h. That is 3.5 kW of electric heat, or a 15,000 BTU/h input furnace at 80% AFUE.

Adjustment factors

Every factor below is a rule of thumb. They stack by multiplication, so a sunny, poorly insulated room in a hot climate gets 1.584 times the base cooling load before people and cooking are added.

BTU calculator adjustment factors
FactorValueApplies to
Insulation: poor / average / good1.2 / 1.0 / 0.9Cooling and heating
Sun: shaded / average / sunny0.9 / 1.0 / 1.1Cooling
Climate: cool / moderate / hot0.9 / 1.0 / 1.2Cooling
Ceiling heightheight ÷ 8 ftCooling and heating
Each person beyond two+600 BTU/hCooling
Kitchen+4,000 BTU/hCooling
Heating, mild / moderate / cold / very cold30 / 40 / 50 / 60 BTU/h per ft²Heating

Measuring and sizing tips

  • Measure the floor wall to wall. For an L-shaped room, split it into rectangles and add the areas, then enter one rectangle with the same total area.
  • Count the people who are usually in the room at the warmest time of day, not the most it will ever hold.
  • Pick "very sunny" for big west- or south-facing windows with no shade, and "heavily shaded" for rooms under trees or on the north side.
  • Window units below 5,000 BTU/h are uncommon. If the load is well under that, the smallest unit is still the right choice; do not step up.
  • A unit that serves an open plan with a kitchen should be sized for the whole open area, with the kitchen allowance added once.

When to get a Manual J

Use this estimate for a single room, a window unit or a space heater. For a new central system, a heat pump replacement, an addition or a whole-house mini-split layout, have a contractor run ACCA Manual J (and Manual S for equipment selection). The International Residential Code (Section M1401.3) calls for heating and cooling equipment sized with Manual S from Manual J loads, and many building departments ask for the calculation with the mechanical permit. An oversized system costs more, short-cycles and leaves the house humid. If a contractor proposes simply matching the old unit's tonnage, ask for the load calculation.

Sources

Frequently asked questions

How many BTU do I need per square foot?

A common rule of thumb is 20 BTU/h of cooling per square foot of floor with an 8 ft ceiling, but small rooms need more per square foot: the ENERGY STAR chart asks for 5,000 BTU/h for a 100–150 ft² room. This calculator uses whichever is larger. Add 10% for a very sunny room, take 10% off for a heavily shaded one, add 600 BTU/h for each person beyond 2, and add 4,000 BTU/h for a kitchen.

What size air conditioner for a 300 square foot room?

About 8,000 BTU/h for a 300 ft² room with an 8 ft ceiling, average sun and insulation and 2 people. That is a standard 8,000 BTU window unit.

How many tons of AC for a 500 square foot kitchen?

It depends heavily on conditions. A sunny, poorly insulated 500 ft² kitchen with a 10 ft ceiling, 4 people and a hot climate comes to about 29,000 BTU/h, or 2.41 tons, so a 2.5-ton system. The same room with average conditions needs much less.

How many BTU is a ton of air conditioning?

One ton of cooling is 12,000 BTU/h, the heat it takes to melt a ton of ice in a day. For electric heat, 3,412 BTU/h equals 1 kW.

How many BTU per square foot for heating?

Rules of thumb run from about 30 BTU/h per square foot in mild climates to 60 in very cold ones. Older or poorly insulated homes sit at the high end, and tall ceilings scale the load up.

Is a bigger air conditioner better?

No. An oversized AC cools the air so fast that it shuts off before it has removed much moisture, so the room feels cold and clammy and the unit short-cycles. Size to the load, not above it.

What is a Manual J load calculation?

ACCA Manual J is the industry method for sizing heating and cooling equipment. It works room by room from wall, window and ceiling areas, insulation levels, air leakage, duct location and local design temperatures, which a rule of thumb cannot capture.