Electrical calculators

Guide

What size wire for 30, 40, 50 and 60 amp circuits

For a 50 amp circuit, use 8 AWG copper with 75°C-rated terminals, 6 AWG copper if it is NM cable or 60°C terminals, or 6 AWG aluminum. A 30 amp circuit takes 10 AWG copper and a 40 amp circuit 8 AWG copper. The tables below give every common breaker size from NEC Table 310.16, then show when a long run or a continuous load pushes you up a size.

Wire size by breaker rating

Read across from the breaker. The first column is NM cable (Romex), which NEC 334.80 limits to the 60°C ampacity. The second is copper building wire such as THHN in conduit landing on terminals listed for 75°C, which is most modern breakers and panels. The third is aluminum at 75°C.

Minimum conductor by NEC 2023 Table 310.16 and 240.4(D), for runs short enough that voltage drop does not matter, 30°C ambient, not more than three current-carrying conductors.
BreakerCopper, 60°C (NM cable)Copper, 75°CAluminum, 75°C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
25 A10 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A1 AWG3 AWG1 AWG

The small sizes are set by the breaker limits in NEC 240.4(D), not by the table: 14 AWG copper on 15 A, 12 AWG copper on 20 A, 10 AWG copper on 30 A, and 12 AWG aluminum on 15 A, 10 AWG aluminum on 25 A. That is why 30 A aluminum jumps to 8 AWG.

The table sizes the wire to the full breaker rating. NEC 240.4(B) also lets a conductor whose ampacity falls between two standard breaker sizes go on the next size up, up to 800 A, as long as the circuit is not a multioutlet branch circuit for plug-in loads and the load itself does not exceed the conductor's ampacity. That is how 6 AWG NM cable (55 A) can be protected by a 60 A breaker when the load it serves is no more than 55 A. Continuous loads still need wire rated for 125% of the load. The wire size calculator applies that rule when you enter the load.

Common circuits and the wire they take

Appliance circuits are sized from the nameplate. Dryers and ranges list the circuit they need; the figures below are typical, and the label on the appliance governs. Water heaters and EV chargers are continuous loads, so the circuit is sized at 125% of their current.

Breaker and minimum copper size; continuous loads per NEC 210.19(A)(1), 422.13 and 625.41.
CircuitLoadBreakerNM cableCopper, 75°C
Electric dryerTypically a 30 A circuit (nameplate)30 A10 AWG10 AWG
Electric range, smallerTypically a 40 A circuit (nameplate)40 A8 AWG8 AWG
Electric range, largerTypically a 50 A circuit (nameplate)50 A6 AWG8 AWG
4,500 W water heater18.75 A × 125% = 23.44 A25 A10 AWG10 AWG
32 A EV charger32 A × 125% = 40 A40 A8 AWG8 AWG
40 A EV charger40 A × 125% = 50 A50 A6 AWG8 AWG
48 A EV charger48 A × 125% = 60 A60 A4 AWG6 AWG

Ranges and dryers usually need a 4-wire circuit (two hots, neutral and ground) in new work; check the appliance instructions for the cable type. EV chargers often let you set the current to match the circuit you have; set it to no more than the breaker rating divided by 1.25.

Why NM cable and THHN give different answers

Table 310.16 has three columns, 60°C, 75°C and 90°C, and a conductor can only be used at the rating of the weakest part of the circuit. NEC 110.14(C) sends circuits of 100 A or less to the 60°C column unless the breaker and the equipment terminals are listed for 75°C, which most current equipment is. NM cable is held to the 60°C column by 334.80 no matter what the terminals are rated. So 8 AWG copper is a 50 A conductor as THHN on 75°C terminals but a 40 A conductor as NM cable.

When to go up a size

Long runs. Voltage drop is not a code limit for most circuits, but the NEC's informational notes suggest keeping a branch circuit under 3%. A 50 A load at 240 V shows how quickly distance adds up:

50 A, 240 V single-phase, copper, 75°C terminations, one-way distance, 3% drop limit.
RunMinimum sizeIts dropSize for 3%Its drop
100 ft8 AWG3.26%6 AWG2.05%
150 ft8 AWG4.88%4 AWG1.93%
200 ft8 AWG6.51%4 AWG2.58%

Heat and bundling. Table 310.16 assumes a 30°C (86°F) ambient and no more than three current-carrying conductors together. A hot attic, a conduit on a sunny roof or several cables bundled through the same bored holes all lower the ampacity, and the corrections in NEC 310.15 can push the wire up a size or more.

Main services. For the service conductors or main feeder of a house, NEC 310.12 lets you size to 83% of the service rating, which is why a 100 A service often runs on 2 AWG aluminum. That allowance does not apply to subpanels or branch circuits.

Electrical work usually needs a permit, and in many places a licensed electrician. Use these sizes to plan the job or check a quote, then follow the code edition your town has adopted.

Sources

  • NFPA 70, National Electrical Code, 2023: Table 310.16 (ampacity), 240.4(B) and (D) (overcurrent protection of conductors), 110.14(C) (termination temperature), 334.80 (NM cable), 210.19(A)(1) and 210.20(A) (continuous loads), 422.13 (water heaters), 625.41 (EV equipment), 310.12 (dwelling services)
  • Ampacity values as tabulated in our wire ampacity chart

Frequently asked questions

What size wire for a 50 amp breaker?

8 AWG copper (50 A in the 75°C column) when the conductors are individual wires such as THHN landing on 75°C-rated terminals; 6 AWG copper for NM cable, which is limited to the 60°C column; 6 AWG aluminum at 75°C.

Can I use 10 gauge wire on a 40 amp breaker?

No. 10 AWG copper is rated 35 A at 75°C and 30 A at 60°C, and NEC 240.4(D) caps it at a 30 A breaker in any case. A 40 A circuit needs 8 AWG copper.

Is 8 gauge wire good for 50 amps?

Only as individual conductors (THHN/THWN) on terminals listed for 75°C, where 8 AWG copper is rated 50 A. As NM cable it is rated 40 A, so a 50 A NM circuit needs 6 AWG.

What size wire for 50 amps at 100 feet?

At 240 V the minimum 8 AWG copper drops 3.26% over a 100 ft one-way run, over the 3% guideline, so go to 6 AWG copper (2.05%).

What size aluminum wire for a 100 amp subpanel?

1 AWG aluminum (100 A at 75°C). The 83% rule of NEC 310.12 that allows 2 AWG aluminum (90 A) applies only to a dwelling's main service or a feeder that carries the whole house load, not to a subpanel feeder.

Do I size the wire for the breaker or the load?

The wire must be protected by the breaker, so it is sized at least to the breaker rating, with the 240.4(D) caps on small wires. The breaker itself is sized to the load, at 125% for continuous loads such as EV chargers and water heaters.

Calculators and charts for this guide

More electrical guides